THERMOPLUS

MINERAL BASE HEAT TRANSFER FULID

Product Description

THERMOPLUS heat transfer oils are high performance products intended for use in closed indirect heating installations. They are formulated from highly refined base stocks that are resistant to thermal cracking and chemical oxidation. They have good heat transfer efficiency and their viscosities are such that they can be pumped readily at both start-up and operating temperatures. The flash points of these oils will not decrease significantly in service because of their resistance to thermal cracking at the operating temperatures for which they are recommended. The THERMOPLUS products are very thermally stable and are capable of an extremely long service life without deposit formation or viscosity increase. They demonstrate specific heats and thermal conductivities that provide more rapid heat dissipation. THERMOPLUS heat transfer oils are recommended for use in both closed and open, cold-oil sealed, indirect heating and cooling systems in all kinds of industrial processes.

Applications

 THERMOPLUS heat transfer oils should not be mixed with other oils since this may impair the excellent thermal and oxidation stability of the THERMOPLUS oils, cause a change in other properties, and complicate the interpretation of analyses made to determine the oil's useful life. If the oils are used above their recommended maximum temperatures, vapor lock may result unless the system is designed to operate at the higher temperature by pressurizing with an inert gas such as nitrogen. However, at higher temperatures, fluid life will be shortened because the rate of thermal degradation increases markedly as temperatures rise above the recommended limit. In well-designed systems the temperature of the oil film surrounding the heating element should be about 15⁰C to 30⁰C above the bulk oil temperature. If higher than this, the service life of the oil may be shortened and sludge and coke may be deposited which would interfere with the heat transfer rates. As with other mineral oils, THERMOPLUS heat transfer oils should be used only in systems with forced circulation. Systems that depend on convection for circulation of the heat transfer medium do not provide a rapid enough flow to prevent local overheating and rapid deterioration of the oil. Further, these oils are not recommended for use in open systems where hot oil is exposed directly to the air. THERMOPLUS can be used in open and closed installations where the bulk oil temperature ranges are as outlined in the table below and where minimum shutdown temperatures are not below -7⁰C.

·       Bulk Oil Temperature Ranges for THERMOPLUS, Closed Systems (-7⁰C to 315⁰C), Open Systems (-7⁰C to 180⁰C)

·       Closed, cold-oil sealed, indirect heating and cooling systems in all kinds of industrial processes operating at bulk oil temperatures up to the maximum temperatures quoted in the table above and at atmospheric pressure.

·       Open systems provided the bulk temperatures do not exceed the maximum temperatures quoted in the table above.

Typical Properties

 

 

Viscosity, ASTM D 445

 

cSt @ 40⁰C

30.4

cSt @ 100⁰C

5.4

Pour Point, ⁰C, ASTM D 97

-7

Flash Point, ⁰C, ASTM D 92

245

Specific Gravity @29⁰C kg/l, ASTM D 4052

0.857

Micro-Conrad’s son Residue, wt %, D4530

0.05 (max)

Copper strip corrosion 3hr @ 100 oc (astm) , max

1

Neutralization number mg koh/gm, max

0.15

Specific heat kcal/kg ⁰C at

260⁰C

0.741

280⁰C

0.761

300⁰C

0.791

Thermal conductivity, kcal/hr-mt ⁰C at

260⁰C

0.1

280⁰C

0.099

300⁰C

0.097